{"searchBar":{"inputPlaceholder":"キーワードを入力して「検索」ボタンをクリック","searchBtn":"検索","error":"キーワードを入力してください。"}}
{}
{}
FAQを参照する

TOSHIBA MACHINE CO.,LTD. PROVISOR TC200

TOSHIBA MACHINE CO.,LTD. PROVISOR TC200


When replacing the cable (RS-232C) used for GP2000/77R/70 series to GP3000 series,
System Configuration Diagram of GP2000/77R/70 series
Connect to COM1.
System Configuration Diagram of GP3000 series


Important notes for the replacement of the cable from GP2000/77R/70 series to GP3000 series *Be sure to read here.
When replacing the hardware from GP2000/77R/70 series to GP3000 series, there are important notes shown below.
Communication settings
-Initial settings between GP-PRO/PB3 and GP-Pro EX are different as below.
GP-Pro/PB3
GP-Pro EX
Send wait
0 msec
0 msec
Time out
10sec
3sec
Retry
2
2
Supported devices
-For GP-Pro EX,the notation of word device differs.Also, the notation of Node differ.
GP-Pro/PB3
GP-Pro EX

Bit

XF7F
XF7F

Word

XWF7
XF7W
Warning messages of [Project Conveter]
-When the project file of GP-PRO/PB3 will be converted by [Project converter], these messages will appear in following cases.
Warning Message
Description
Baudrate which cannot communicate is chosen. It is changed into 9600bps which is a default value.
In case the Baudrate of the project file created on GP-Pro/PB3 is set 187500bps, it is changed to 9600bps.
Unsupported device address is defined. Device address will appear as -Undefined-.This message appears when the device address out of the range supported by GP-Pro EX is specified. For example, it appears if the address, XFFF which does not exist in the PLC is set. Please specify the supported device address.


Please refer to

このFAQはお役に立ちましたか?