Error Details | The error message [RHAA067(Node Name): Response timed out for initial communication command] appeared on the GP3000 screen. | Causes | 1. | The communication settings of the GP unit and those of the device/PLC are not matched. | 2. | Wiring has problems such as a wrong wire connection or a loose connection. | 3. | Selection of Device/PLC is wrong. | 4. | The power of Device/PLC is not ON, or it is reset. | | Actions | 1. | Check if the communication settings of the GP unit and those of the device/PLC are matched. For setting examples, refer to the GP-Pro EX Device/PLC Connection Manual. | 2. | Check the wiring, cable connection, and connecter's insertion. For details of cable diagrams between a GP unit and a device/PLC, please refer to the GP-Pro EX Device/PLC Connection Manual. For use of the COM2 port, check if the Online Adapter (CA4-ADPONL-01) is connected. | 3. | Check the type of the device/PLC to be connected to the GP unit in GP-Pro EX. | | | |